Dwyer 26110 process controller with SSR output, selectable inputs (thermocouple, RTD, voltage, current), ±0.25% accuracy, and NEMA 4X rated.

Model 26110
Manufacturer Dwyer Instruments
Category Process Controllers
Availability Made to order

Overview

The Dwyer 26110 is a compact industrial process controller for temperature and process monitoring and control applications. It features a single SSR (solid-state relay) output for proportional or on-off control, combined with selectable input options to accommodate thermocouples, RTDs, DC voltage, or DC current signals. The dual LED display shows both process value and setpoint simultaneously, making it ideal for applications requiring precise process management in harsh environments.

Key Features

  • Single SSR output (Output A) for proportional or on-off control
  • Selectable inputs: Thermocouple, RTD, DC voltage, or DC current
  • Dual 4-digit LED displays (0.56" high) for process and setpoint values
  • ±0.25% of span accuracy with ±1 LSB resolution
  • Supply voltage options: 100–240 VAC or 132–240 VDC
  • Alarm relay output (SPST, 3 A @ 240 VAC)
  • NEMA 4X (IP66) front panel rating for corrosion and moisture resistance
  • Operating temperature range: –10 to 55°C

Applications

  • Temperature monitoring and control in HVAC systems
  • Process control in industrial manufacturing
  • Laboratory and test equipment control
  • Food processing and cooking equipment
  • Environmental chamber control
Input Type Options Thermocouple, RTD, DC voltage, DC current
Accuracy ±0.25% of span ±1 least significant digit
Display Two 4-digit, 7-segment LED, 0.56" (14.2 mm) high
Output A SSR (solid-state relay)
Alarm Output SPST relay, 3 A @ 240 VAC
Supply Voltage 100–240 VAC nominal (50–400 Hz, single phase) or 132–240 VDC
Operating Temperature –10 to 55°C (14 to 131°F)
Front Panel Rating NEMA 4X (IP66)
Weight 369 g (13 oz)
Input Impedance Thermocouple: 3 MΩ min; Voltage: 5000 Ω; Current: 10 Ω; RTD: 200 µA max